4-20 mA Thermocouple Transmitter

Exceptional linearity & accuracy at high update rates. DIN Rail mounted, digitally programmable.
Navigation:  Home > Transmitters, 4-20mA
4-20 mA Current Transmitter for Thermocouples
Key Features
  • Factory calibrated for thermocouple types J, K, T, E, N, R, S
  • User selectable 4-20 mA, 0-20 mA or 0-10 Vdc linearized analog output
  • User selectable input span from entire thermocouple range down to 15.0°
  • Highly accurate and repeatable
  • Upscale or downscale open sensor indication
  • Output update rate to 60/sec
Specifications
Laureate 4-20 mA Thermocouple Temperature Transmitter

TC Types Range Conformity Error
J -210°C to +760°C (-347°F to +1400°F) ±0.09°C (±0.16°F)
K -244°C to +1372°C (-408°F to +2501°F) ±0.1°C (±0.17°F)
T 0°C to +400°C (32°F to 752°F)
-257°C to 0°C (-430°F to +32°F)
±0.03°C (±0.05°F)
±0.2°C (±0.36°F)
E -240°C to +1000°C (-400°F to +1830°F) ±0.18°C (±0.32°F)
N -245°C to +1300°C (-410°F to +2370°F) ±0.10°C (±0.17°F)
R -45°C to +1768°C (-49°F to +3214°F) ±0.17°C (±0.31°F)
S -46°C to +1768°C (-51°F to +3213°F) ±0.12°C (±0.22°F)

Analog Input
Calibration
Input resistance
Input current
Max lead resistance
Overall accuracy
Span tempco
Ref junction tempco
Overvoltage protection
NMR at 50/60 Hz
CMR, DC-60 Hz
CMV, DC-60 Hz
Open sensor indication
NIST Monograph 125 (IPTS-68)
1 GΩ
100 pA
1 kΩ max for rated accuracy
±0.01 of full scale ±2 counts
±0.003% of reading/°C
±0.02 deg/deg
125 Vac
80 dB plus selectable filter from 80 ms to 9.6 s time constant
120 dB with 500Ω imbalance
250 Vac from power and earth grounds
0 mA or > 20 mA output, selectable
Analog Output (standard)
Output Levels
Compliance, 4-20 mA
Compliance, 0-10V
Output Resolution
Output Accuracy
Output Isolation
Step response time
4-20 mA, 0-20 mA, 0-10 Vdc (jumper selectable)
10V ( 0-500Ω load )
2 mA ( 5 kΩ load or higher)
16 bits (65,536 steps)
0.02% of output span plus conversion accuracy
250V rms working, 2.3 kV rms per 1 minute test
50 ms
Dual Relay Output (standard)
Relay Type
Load Rating
Two solid state relays, SPST, normally open, Form A
130 mA at 140 Vac or 180 Vdc
Serial Communications (standard)
Signal Types
Data Rates
Output Isolation
Serial Protocols
Modbus Modes
Modbus Compliance
Digital Addressing
RS232 or RS485 (half or full duplex)
300, 600, 1200, 2400, 4800, 9600, 19200 baud
250V rms working, 2.3 kV rms per 1 min test
Modbus RTU, Modbus ASCII, Laurel ASCII
RTU or ASCII
Modbus over Serial Line Specification V1.0 (2002)
247 Modbus addresses.
Up to 32 devices on an RS485 line w/o a repeater.
Power Input
Standard Power
Low Power Option
Power Frequency
Power Isolation
Power Consumption
85-264 Vac or 90-300 Vdc (DC operation not UL approved)
10-48 Vdc or 12-32 Vac
DC or 47-63 Hz
250V rms working, 2.3 kV rms per 1 min test
2W typical
Mechanical
Dimensions
Mounting
Electrical Connections
129 x 104 x 22.5 mm case
35 mm rail per DIN EN 50022
Plug-in screw-clamp connectors
Environmental
Operating Temperature
Storage Temperature
Relative Humidity
Cooling Required
0°C to 55°C
-40°C to 85°C
95% at 40°C, non-condensing
Mount transmitters with ventilation holes at top and bottom.
Leave 6 mm (1/4") between transmitters, or force air with a fan.

Pinout

Laureate 4-20 mA Thermocouple Temperature Transmitter

pin out for 4-20 transmitter for AC RMS Voltage

Operation as a Fast ON/OFF Controller or Supervisory Monitor
With the optional dual solid state relay output option, which has a typical response time of only 17 ms, Laureate temperature meters and transmitters can serve as extremely fast and accurate ON/OFF controllers for closed-loop temperature control. They can also serve as supervisory process monitors and provide alarms or shutoffs when processes exceed normal limits. Temperature controller operation of Laureate temperature meters and transmitters
Multiple setpoint operating modes are individually selectable for each relay, as explained in the dual-setpoint controller page. Relay duty cycles and chatter can be minimized with programmable hysteresis and time delays. A band deviation operating mode can be selected for each relay, where an alarm is generated whenever the reading is a selected number of counts above or below the setpoint. The relay modes have to be non-latching, since 4-20 mA temperature transmitters do not offer external reset.