4-20 mA Thermocouple Transmitter
Exceptional linearity & accuracy at high update rates.
DIN Rail mounted, digitally programmable.
Key Features
- Factory calibrated for thermocouple types J, K, T, E, N, R, S
- User selectable 4-20 mA, 0-20 mA or 0-10 Vdc linearized analog output
- User selectable input span from entire thermocouple range down to 15.0°
- Highly accurate and repeatable
- Upscale or downscale open sensor indication
- Output update rate to 60/sec
Specifications
Laureate 4-20 mA Thermocouple Temperature Transmitter
| TC Types |
Range |
Conformity Error |
| J |
-210°C to +760°C (-347°F to +1400°F) |
±0.09°C (±0.16°F) |
| K |
-244°C to +1372°C (-408°F to +2501°F) |
±0.1°C (±0.17°F) |
| T |
0°C to +400°C (32°F to 752°F)
-257°C to 0°C (-430°F to +32°F) |
±0.03°C (±0.05°F)
±0.2°C (±0.36°F) |
| E |
-240°C to +1000°C (-400°F to +1830°F) |
±0.18°C (±0.32°F) |
| N |
-245°C to +1300°C (-410°F to +2370°F) |
±0.10°C (±0.17°F) |
| R |
-45°C to +1768°C (-49°F to +3214°F) |
±0.17°C (±0.31°F) |
| S |
-46°C to +1768°C (-51°F to +3213°F) |
±0.12°C (±0.22°F) |
| Analog Input |
Calibration
Input resistance
Input current
Max lead resistance
Overall accuracy
Span tempco
Ref junction tempco
Overvoltage protection
NMR at 50/60 Hz
CMR, DC-60 Hz
CMV, DC-60 Hz
Open sensor indication |
NIST Monograph 125 (IPTS-68)
1 GΩ
100 pA
1 kΩ max for rated accuracy
±0.01 of full scale ±2 counts
±0.003% of reading/°C
±0.02 deg/deg
125 Vac
80 dB plus selectable filter from 80 ms to 9.6 s time constant
120 dB with 500Ω imbalance
250 Vac from power and earth grounds
0 mA or > 20 mA output, selectable |
| Analog Output (standard) |
Output Levels
Compliance, 4-20 mA
Compliance, 0-10V
Output Resolution
Output Accuracy
Output Isolation
Step response time |
4-20 mA, 0-20 mA, 0-10 Vdc (jumper selectable)
10V ( 0-500Ω load )
2 mA ( 5 kΩ load or higher)
16 bits (65,536 steps)
0.02% of output span plus conversion accuracy
250V rms working, 2.3 kV rms per 1 minute test
50 ms |
| Dual Relay Output (standard) |
Relay Type
Load Rating |
Two solid state relays, SPST, normally open, Form A
130 mA at 140 Vac or 180 Vdc |
| Serial Communications (standard) |
Signal Types
Data Rates
Output Isolation
Serial Protocols
Modbus Modes
Modbus Compliance
Digital Addressing |
RS232 or RS485 (half or full duplex)
300, 600, 1200, 2400, 4800, 9600, 19200 baud
250V rms working, 2.3 kV rms per 1 min test
Modbus RTU, Modbus ASCII, Laurel ASCII
RTU or ASCII
Modbus over Serial Line Specification V1.0 (2002)
247 Modbus addresses.
Up to 32 devices on an RS485 line w/o a repeater. |
| Power Input |
Standard Power
Low Power Option
Power Frequency
Power Isolation
Power Consumption |
85-264 Vac or 90-300 Vdc (DC operation not UL approved)
10-48 Vdc or 12-32 Vac
DC or 47-63 Hz
250V rms working, 2.3 kV rms per 1 min test
2W typical |
| Mechanical |
Dimensions
Mounting
Electrical Connections |
129 x 104 x 22.5 mm case
35 mm rail per DIN EN 50022
Plug-in screw-clamp connectors |
| Environmental |
Operating Temperature
Storage Temperature
Relative Humidity
Cooling Required |
0°C to 55°C
-40°C to 85°C
95% at 40°C, non-condensing
Mount transmitters with ventilation holes at top and bottom.
Leave 6 mm (1/4") between transmitters, or force air with a fan. |
Pinout Laureate 4-20 mA Thermocouple Temperature Transmitter
Operation as a Fast ON/OFF Controller or Supervisory Monitor
| With the optional dual solid state relay output option, which has a typical response time of only 17 ms, Laureate temperature meters and transmitters can serve as extremely fast and accurate ON/OFF controllers for closed-loop temperature control. They can also serve as supervisory process monitors and provide alarms or shutoffs when processes exceed normal limits. |
 |
|
Multiple setpoint operating modes are individually selectable for each relay, as explained in the dual-setpoint controller page. Relay duty cycles and chatter can be minimized with programmable hysteresis and time delays. A band deviation operating mode can be selected for each relay, where an alarm is generated whenever the reading is a selected number of counts above or below the setpoint. The relay modes have to be non-latching, since 4-20 mA temperature transmitters do not offer external reset. |
|