Modbus & Serial Output Transmitter for Duty Cycle Input
Transmits ON or OFF period in percent of total period.
DIN Rail mounted, digitally programmable.
Key Features
- Selectable Modbus or Laurel ASCII protocol
- Modbus RTU or ASCII modes, 2-wire connection, up to 247 digital addresses
- Transmits ON or OFF period as a percentage of total period
- Resolution of 1%, 0.1% or 0.01%
- Frequencies from .005 Hz to 10 kHz
- Triggers on positive or negative pulse edges
- Optional dual solid state relays for alarm or control
- 5V, 10V or 24V dc sensor excitation output, isolated
- Dual solid state relays for alarm or control, isolated
- Dual solid state relays for alarm or control, isolated
- 0-10V, 4-20 mA or 0-20 mA transmitter output, isolated
- Universal AC power, 85-264 Vac
Laureate Modbus & Serial Output Transmitter for Duty Cycle Input
|
Pulse Input |
Types
Signal Ground
Minimum Signal
Maximum Signal
Maximum Frequency
Contact Debounce |
AC,
pulses from NPN, PNP transistors, contact closures,
magnetic pickups.
Common ground for channels A & B
Nine ranges from (-12 to +12 mV) to (+1.25 to +2.1V)
250 Vac
1 MHz, 30 kHz, 250 Hz (selectable)
0, 3, 50 ms (selectable) |
|
Duty
Cycle Mode |
Item Displayed
Display Units
Frequency Range
Input
Accuracy
Maximum Timing Interval |
ON
or OFF duty cycle of periodic pulse waveshape
1%, 0.1%, 0.01%
0.005 Hz to 50 kHz
0.01%, 0.005 Hz to 500 Hz, 0.1% at 5 kHz, 1% at 50 kHz
199.99 s |
|
Update Rate |
Conversion Interval
Gate Time
Time Before Zero Output |
Gate
time + 30 ms + 0-2 signal periods
Selectable 10 ms to 199.99 s
Selectable 10 ms to 199.99 s |
|
Serial Data I/O
(standard) |
Signal levels
Data Rates
Output Isolation
Serial Protocols
Devices on RS-485 Line
Modbus Addresses
Modbus Modes
Modbus Compliance |
RS232 or RS485 (half duplex)
300, 600, 1200, 2400, 4800, 9600, 19200 baud
250V rms working, 2.3 kV rms per 1 min test
Modbus RTU, Modbus ASCII, Laurel ASCII (selectable)
32 max without a repeater.
247 max
RTU or ASCII, 2-wire.
Modbus over Serial Line Specification V1.0 (2002). |
|
Transducer Excitation Output (standard) |
Output Levels
Output Isolation |
5V@100 mA, 10 @120 mA, 24V@50 mA (jumper
selectable)
50V from signal ground |
|
Dual Relay Output (standard) |
Relay Type
Load Rating |
Two solid state relays, SPST, normally open,
Form A
130 mA at 140 Vac or 180 Vdc |
|
Analog Output (standard) |
Output Levels
Compliance, 4-20 mA
Compliance, 0-10V
Output Resolution
Output Accuracy
Output Isolation |
4-20 mA, 0-20 mA, 0-10 Vdc (jumper selectable)
10V ( 0-500 ohm load )
2 mA ( 5 kOhm load or higher)
16 bits (65,536 steps)
0.02% of output span plus conversion accuracy
250V rms working, 2.3 kV rms per 1 minute test |
|
Power Input |
Standard Power
Low Power Option
Power Frequency
Power Isolation
Power Consumption |
85-264 Vac or 90-300 Vdc (DC operation not UL
approved)
10-48 Vdc or 12-32 Vac
DC or 47-63 Hz
250V rms working, 2.3 kV rms per 1 min test
2W typical, 3W with max excitation output |
|
Mechanical |
Dimensions
Mounting
Electrical Connections |
129 x 104 x 22.5 mm
case
35 mm rail per DIN EN 50022
Plug-in screw-clamp connectors |
|
Environmental |
Operating
Temperature
Storage Temperature
Relative Humidity
Cooling Required |
0°C
to 55°C
-40°C to 85°C
95% at 40°C, non-condensing
Mount transmitters with ventilation holes at top and bottom.
Leave 6 mm (1/4") between transmitters, or force air with a fan. |
Pinout
Laureate Modbus & Serial Output Transmitter for Duty Cycle Input
|