Modbus & Serial Output Transmitter for Time of Single or Accumulated Events

Resolution to 0.2 µs. Duration to 999,999 hrs. DIN Rail mounted, digitally programmable.
Navigation:  Home > Transmitter-modbus>
Serial ASCII or Modbus Transmitter, Stopwatch Input
Key Features
  • Triggers on positive or negative pulse edges
  • DIN rail mount housing only 22.5 mm wide
  • Plug-in screw-clamp connectors
  • Easy setup with PC-based Instrument Setup Software
  • 5V, 10V or 24V dc sensor excitation output, isolated
  • Dual solid state relays for alarm or control, isolated
  • Selectable Modbus or Laurel ASCII protocol
  • Modbus RTU or ASCII modes, 2-wire connection, up to 247 digital addresses.
  • Times single event time or accumulated time of all events.
  • Timing resolution to 0.2 µs
  • Timing duration to 999,999 hrs
Pulse Input
Types

Ch A Frequency, Max
Ch B Frequency, Max
Signal Ground
Minimum Signal
Maximum Signal
Maximum Frequency
Contact Debounce
Time Base Accuracy
Span Tempco
Long-term Drift
AC, pulses from NPN, PNP transistors, contact closures,
magnetic pickups.
1 MHz
250 kHz
Common ground for channels A & B
Nine ranges from (-12 to +12 mV) to (+1.25 to +2.1V)
250 Vac
1 MHz, 30 kHz, 250 Hz (selectable)
0, 3, 50 ms (selectable)
Quartz crystal calibrated to ±2 ppm
±1 ppm/°C (typ)
±5 ppm/year
Stopwatch Operation
Timing Modes:
   With CH A only
   With CH A tied to CH B
   With CH A and CH B

Timing Interval
Timing Resolution
Selectable Decimal Time
Selectable Clock Time
Output Update
Gate Time

+ to + edge, or - to - edge.
+ to - edge, or - to + edge.
+ edge of A to + edge of B, + edge of A to - edge of B,
- edge to A to - edge of B, - edge of A to - edge of B
1 µs to 999,999 hrs
0.2 µs to 1 hr
999999 H, M or S format with decimal point
HH.MM.SS format
Gate time + 30 ms
Programmable from 10 ms to 199.99 s
Serial Data Output (standard)
Signal levels
Data Rates
Output Isolation
Serial Protocols
Devices on RS-485 Line
Modbus Addresses
Modbus Modes
Modbus Compliance
RS232 or RS485 (half duplex)
300, 600, 1200, 2400, 4800, 9600, 19200 baud
250V rms working, 2.3 kV rms per 1 min test
Modbus RTU, Modbus ASCII, Laurel ASCII (selectable)
32 max without a repeater.
247 max
RTU or ASCII, 2-wire.
Modbus over Serial Line Specification V1.0 (2002)
Transducer Excitation Output (standard)
Output Levels
Output Isolation
5V@100 mA, 10 @120 mA, 24V@50 mA (jumper selectable)
50V from signal ground
Dual Relay Output (standard)
Relay Type
Load Rating
Two solid state relays, SPST, normally open, Form A
120 mA at 130 Vac or 170 Vdc, 28 ohms series resistance
Analog Output (standard)
Output Levels
Compliance, 4-20 mA
Compliance, 0-10V
Output Resolution
Output Accuracy
Output Isolation
4-20 mA, 0-20 mA, 0-10 Vdc (jumper selectable)
10V ( 0-500 ohm load )
2 mA ( 5 kOhm load or higher)
16 bits (65,536 steps)
0.02% of output span plus conversion accuracy
250V rms working, 2.3 kV rms per 1 minute test
Power Input
Standard Power
Low Power Option
Power Frequency
Power Isolation
Power Consumption
85-264 Vac or 90-300 Vdc (DC operation not UL approved)
10-48 Vdc or 12-32 Vac
DC or 47-63 Hz
250V rms working, 2.3 kV rms per 1 min test
2W typical, 3W with max excitation output
Mechanical
Dimensions
Mounting
Electrical Connections
129 x 104 x 22.5 mm case
35 mm rail per DIN EN 50022
Plug-in screw-clamp connectors
Environmental
Operating Temperature
Storage Temperature
Relative Humidity
Cooling Required
0°C to 55°C
-40°C to 85°C
95% at 40°C, non-condensing
Mount transmitters with ventilation holes at top and bottom.
Leave 6 mm (1/4") between transmitters, or force air with a fan.
Pinout

Laureate Modbus & Serial Output Transmitter for Time of Single or Accumulated Events

feedback