Modbus & Serial Output Thermocouple Transmitter

Exceptional linearity & accuracy at high update rates. DIN Rail mounted, digitally programmable.
Navigation:  Home > Transmitters-modbus
 Modbus Transmitters for thermocouples
Key Features
  • Universal AC switching power supply for 85-264 Vac
  • DIN rail mount housing only 22.5 mm wide
  • Detachable screw-clamp connectors
  • User selectable 4-20 mA, 0-20 mA or 0-10 Vdc linearized analog output
  • Analog output resolution: 0.0015% of span (16 bits)
  • Dual solid state relays for alarm or control, isolated
  • Factory calibrated for thermocouple types J, K, T, E, N, R, S
  • RS232 or RS485 serial communications, half or full duplex, isolated
  • Modbus RTU, Modbus ASCII or Laurel ASCII protocol
  • Highly accurate and repeatable
  • Upscale or downscale open sensor indication
TC Types Range Conformity Error
J -210°C to +760°C (-347°F to +1400°F) ±0.09°C (±0.16°F)
K -244°C to +1372°C (-408°F to +2501°F) ±0.1°C (±0.17°F)
T 0°C to +400°C (32°F to 752°F)
-257°C to 0°C (-430°F to +32°F)
±0.03°C (±0.05°F)
±0.2°C (±0.36°F)
E -240°C to +1000°C (-40°F to +1830°F) ±0.18°C (±0.32°F)
N -245°C to +1300°C (-410°F to +2370°F) ±0.10°C (±0.17°F)
R -45°C to +1768°C (-49°F to +3214°F) ±0.17°C (±0.31°F)
S -46°C to +1768°C (-51°F to +3213°F) ±0.12°C (±0.22°F)

 

Thermocouple Input
Calibration
Input resistance
Input current
Max lead resistance
Overall accuracy
Span tempco
Reference junction tempco
Span tempco
Over-voltage protection
NMR at 50/60 Hz
CMR, DC-60 Hz
CMV, DC-60 Hz
Open sensor indication
NIST Monograph 125 (IPTS-68)
1 GΩ
100 pA
1 kΩ max for rated accuracy
±0.01 of full scale ± 2 counts
±0.003% of reading/°C
±0.02 deg/deg
±0.003% of reading/°C
125 Vac
80 dB plus selectable filter from 80 ms to 9.6 s time constant
120 dB with 500 W imbalance
250 Vac from power and earth grounds
0 mA or > 20 mA output, selectable
Serial Data Output (standard)
Signal levels
Data Rates
Output Isolation
Serial Protocols
Devices on RS485 Line
Modbus Addresses
Modbus Modes
Modbus Compliance
RS232 or RS485 (half duplex)
300, 600, 1200, 2400, 4800, 9600, 19200 baud
250V rms working, 2.3 kV rms per 1 min test
Modbus RTU, Modbus ASCII, Laurel ASCII (selectable)
32 max without a repeater
247 max
RTU or ASCII, 2-wire
Modbus over Serial Line Specification V1.0 (2002)
Analog Output
Output Levels
Compliance, 4-20 mA
Compliance, 0-10V
Output Resolution
Output Accuracy
Output Isolation
0-20 mA or  0-10 Vdc (selectable)
10V ( 0-500 ohm load )
2 mA ( 5 kΩ load )
16 bits (65,536 steps)
0.02% of output span plus conversion accuracy
250V rms working, 2.3 kV rms per 1 minute test
Dual Relay Output (standard)
Relay Type
Load Rating
Two solid state relays, SPST, normally open, Form A
130 mA at 140 Vac or 180 Vdc
Power Input
Standard Power
Low Power Option
Power Frequency
Power Isolation
Power Consumption
85-264 Vac or 90-300 Vdc (DC operation not UL approved)
10-48 Vdc or 12-32 Vac
DC or 47-63 Hz
250V rms working, 2.3 kV rms per 1 min test
2W typical, 3W with max excitation output
Mechanical
Dimensions
Mounting
Electrical Connections
129 x 104 x 22.5 mm case
35 mm rail per DIN EN 50022
Plug-in screw-clamp connectors
Environmental
Operating Temperature
Storage Temperature
Relative Humidity
Cooling Required
0°C to 55°C
-40°C to 85°C
95% at 40°C, non-condensing
Mount transmitters with ventilation holes at top and bottom.
Leave 6 mm (1/4") between transmitters, or force air with a fan.
Pinout

Laureate Modbus & Serial Output Thermocouple Temperature Transmitter

Pinout of thermocouple temperature transmitter