| Pulse Input |
Types
Ch A Frequency, Max
Ch B Frequency, Max
Signal Ground
Minimum Signal
Maximum Signal
Maximum Frequency
Contact Debounce |
AC, pulses from NPN, PNP transistors, contact closures,
magnetic pickups.
1 MHz
250 kHz
Common ground for channels A & B
Nine ranges from (-12 to +12 mV) to (+1.25 to +2.1V)
250 Vac
1 MHz, 30 kHz, 250 Hz (selectable)
0, 3, 50 ms (selectable) |
| Serial Data Output (standard) |
Signal levels
Data Rates
Output Isolation
Serial Protocols
Devices on RS485 Line
Modbus Addresses
Modbus Modes
Modbus Compliance |
RS232 or RS485 (half duplex)
300, 600, 1200, 2400, 4800, 9600, 19200 baud
250V rms working, 2.3 kV rms per 1 min test
Modbus RTU, Modbus ASCII, Laurel ASCII (selectable)
32 max without a repeater
247 max
RTU or ASCII, 2-wire
Modbus over Serial Line Specification V1.0 (2002) |
| Transducer Excitation Output (standard) |
Output Levels
Output Isolation |
5V@100 mA, 10V@120 mA, 24V@50 mA (jumper selectable)
50V from signal ground |
| Dual Relay Output (standard) |
Relay Type
Load Rating |
Two solid state relays, SPST, normally open, Form A
130 mA at 140 Vac or 180 Vdc |
| Analog Output |
Output Levels
Compliance, 4-20 mA
Compliance, 0-10V
Output Resolution
Output Accuracy
Output Isolation |
0-20 mA orĀ 0-10 Vdc (selectable)
10V ( 0-500 ohm load )
2 mA ( 5 kOhm load )
16 bits (65,536 steps)
0.02% of output span plus conversion accuracy
250V rms working, 2.3 kV rms per 1 minute test |
| Power Input |
Standard Power
Low Power Option
Power Frequency
Power Isolation
Power Consumption |
85-264 Vac or 90-300 Vdc (DC operation not UL approved)
10-48 Vdc or 12-32 Vac
DC or 47-63 Hz
250V rms working, 2.3 kV rms per 1 min test
2W typical, 3W with max excitation output |
| Mechanical |
Dimensions
Mounting
Electrical Connections |
129 x 104 x 22.5 mm case
35 mm rail per DIN EN 50022
Plug-in screw-clamp connectors |
| Environmental |
Operating Temperature
Storage Temperature
Relative Humidity
Cooling Required |
0°C to 55°C
-40°C to 85°C
95% at 40°C, non-condensing
Mount transmitters with ventilation holes at top and bottom.
Leave 6 mm (1/4") between transmitters, or force air with a fan. |